With a ground fault there'd be 0 across one and 480 across the other two. If there's one burnt out lamp there'd be 240V across the remaining two.. Attached is a copy of the wiring diagram for these ground indication lights.. 480V, 300KW, BESS System breaker ground fault trip 3. power2engineer; Sep 21, 2024;. jraef: On the disconnect is says three wire 480. From my experience that is either a ungrounded delta or a floating wye on the secondary. On the line drawing it is T9. They are showing a Delta-Wye transformer and I believe that it is accurate. I will look to see if we have any wiring diagrams on the install itself.
INSTALLATION: IMPORTANT: Installation manual for use by qualified personnel or an electrician only. Step 1: Disconnect power to the pedestal prior to any service.Access terminal block and breaker dinrail in pedestals. Step 2: Installing CT: Determine which circuit will be monitored by the ground fault relay. The CT must be placed around all hot leads in the circuit including neutral, if.. An actual ground fault with water leading the list for the cause of the ground fault. A defective GFP relay or other protection device, defective CT or an open in the CT secondary wiring. A fault in 208/120 VAC distribution in a properly installed system will not operate a 480/277 GFP